Fibre Reinforced Facade Encyclopedia: Installation

A weather barrier is the continuous water resisting, air resisting layer applied to the face of the backing wall behind a cavity, also called a weather resistive barrier or a sarking membrane. On a drained and ventilated facade it is not a backup layer in any meaningful sense. The outer panels shed most of the water and control the pressure, but water will pass the joints, and the barrier is the surface that stops it reaching the building. On a rainscreen, the weather barrier is the weatherline.

If the barrier is not continuous, the cavity turns from a drainage path into a distribution system, carrying water sideways and downwards to whichever penetration it finds first.

At a glance

PropertyTypical valueNote
FunctionWater resistance, air tightness, vapour transmissionAll three considered together
PositionOn the face of the backing wall, behind the cavityOutboard of insulation in most drained build-ups
Vapour permeanceTypically above 1.14 micrograms per newton secondClass 4 vapour permeable under AS 4200.1
Water barrier classHigh water barrier class preferredClassified under AS/NZS 4200.1
Air permeabilitySealed and taped as a continuous air barrierContributes to the building air tightness target
LapsTypically 150 mm horizontal, 100 mm verticalShingled, upper sheet over lower
FixingMechanically fixed and taped, or self-adheredFixings through it are penetrations to seal
Ultraviolet exposure limitTypically 30 to 90 days before claddingManufacturer specific; routinely exceeded
FireA combustible layer unless tested otherwiseAssessed against the NCC external wall provisions

Why the barrier is the real weatherline

A drained and ventilated facade works because the outer skin is deliberately imperfect. Open or lightly sealed joints let air move in and out so cavity pressure approaches external pressure, removing the difference that would drive water through the joints. Some water still enters, as spray, as capillary flow along a joint face, and as run-off down the back of the panel. The cavity catches it, it drains down the inner face, and it is released at flashings and drainage points. The layer that catches and sheds it is the weather barrier.

This matters for how the barrier is treated on site. Understood as a wrap that keeps the frame dry until the cladding arrives, it will be fixed loosely, torn by scaffold and following trades, penetrated by services with no attention to sealing, and left with laps running the wrong way. Understood as the weatherline, it is set out, lapped shingle fashion, taped, sealed at every penetration and inspected before it is covered. It is also the air barrier in most contemporary build-ups, and air leakage carries far more moisture into a wall than vapour diffusion does.

Vapour permeability and where the layers sit

A wall assembly has to dry, and behind a drained facade that drying path is outwards through the barrier into the ventilated cavity, which is why the membrane there is normally vapour permeable rather than a vapour barrier: it resists liquid water while letting vapour diffuse through. Getting that backwards is a classic failure. A vapour impermeable membrane on the cold side of insulation, in a heating dominated climate or a building with high internal moisture, becomes a condensing surface and the wall wets from the inside with no way to dry. Australian practice is set out in AS 4200.1 and AS 4200.2 and in the National Construction Code condensation management provisions (check the edition adopted in your jurisdiction), which classify membranes by vapour permeance and water barrier performance. The ventilated cavity is part of this system: its depth, continuity and openings at top and bottom determine whether moisture leaving the barrier is actually removed, so the barrier and the cavity are designed together or neither works.

Continuity, laps, penetrations and terminations

  • Laps shingled so water runs over the joint, not into it, with the upper sheet always outboard
  • Taped laps, with a tape the membrane manufacturer has tested with that membrane, applied to a clean dry surface and rolled
  • Every bracket, rail fixing, service penetration and fastener sealed with tape, gasket or liquid flashing
  • Openings wrapped so the barrier laps over the head flashing and under the sill flashing, and returns into the reveal
  • Terminations at base, parapet and every change of plane detailed as a joint to another element, not cut off
  • Continuity across the slab edge, the junction most often left open and the one that carries the most water
  • Interfaces with the roof underlay, podium waterproofing and adjacent wall systems agreed and drawn

Fire performance of the membrane itself

Under the National Construction Code, external walls of Type A and Type B construction are required to be non-combustible, and the code sets out which materials and thin layers are permitted within that requirement. Sarking-type materials are addressed specifically, and a membrane relied on in such a wall is commonly required to have a flammability index not exceeding 5 when tested to AS 1530.2, with the report available. Some membranes are tested more extensively, including as part of a full-scale assembly test to AS 5113. Whichever route is used, the claim must name the standard and the testing body.

Where the wall is justified by a performance solution rather than the deemed-to-satisfy provisions, the membrane is one of the materials in the tested or assessed assembly and cannot be substituted afterwards without invalidating the basis of the approval. That is the most common way a compliant design becomes a non-compliant building.

Specifying it

Name the membrane by product and manufacturer, or specify it by classification: vapour permeance class to AS 4200.1, water barrier class, air permeability, and the flammability index or fire test evidence required for the wall type. Require the manufacturer’s own tape and accessories, state the lap dimensions and fixing method, and require sealing of every penetration with a named product.

Standards and references

  • AS/NZS 4200.1 Pliable building membranes and underlays, materials, and AS 4200.2 installation
  • AS 1530.2 Test for flammability of materials, flammability index, as applied to sarking-type materials
  • NCC 2022 Volume One Specification 7 and the external wall provisions, and Part F8 condensation management (check the edition adopted in your jurisdiction)
  • AS 5113 Classification of external walls of buildings based on reaction-to-fire performance
  • AS/NZS 4284 Testing of building facades, water penetration and air infiltration of the assembled system
  • AS 4654.2 Waterproofing membranes for external above ground use, where the barrier meets waterproofing

Related terms

Questions specifiers ask

Is the weather barrier a backup layer?

On a drained and ventilated facade it is the primary weatherline. The outer panels shed most of the water and equalise pressure across the joints, but water enters the cavity by design, and the barrier is the surface that catches and sheds it. Treating it as a temporary wrap is the root of most failures.

Should the membrane be vapour permeable?

Behind a drained facade, normally yes. The wall dries outwards into the ventilated cavity, so the membrane resists liquid water while letting vapour diffuse through. A vapour impermeable sheet on the cold side of insulation becomes a condensing surface. Classes and their use are set by AS 4200.1 and the NCC condensation provisions.

Does the membrane have to be non-combustible?

It has to be assessed, not assumed. In buildings required to have non-combustible external walls, sarking-type materials are addressed specifically and a membrane is commonly required to have a flammability index of not more than 5 when tested to AS 1530.2. Any fire claim must name the standard and the testing body.

Can a different membrane be substituted on site?

Not where the wall is justified by a performance solution or a full-scale assembly test. The membrane is one of the materials in the tested assembly, and substitution invalidates the basis of the approval. It is a common route from a compliant design to a non-compliant building.

When should the barrier be inspected?

Before the substructure is fixed over it, elevation by elevation, with a photographic record. Once brackets, rails and panels are installed the barrier is inaccessible for the life of the building, and reaching a defect later means facade access and panel removal.